KYN61-40.5 Type Armored Withdrawable AC Metal-Enclosed Switchgear


The KYN61-40.5 type armored withdrawable AC metal-clad switchgear is characterized by the use of a fully insulated vacuum circuit breaker of model ZN85-40.5 and a spring-operated mechanism within the cabinet. It can also be equipped with ABB’s VD4-40.5 and HD4-40.5 switchgear units. The cabinets are assembled from aluminized-zinc coated sheets and cold-rolled steel plates with powder-coating, which enhances the precision of the coordination between the handcart and the cabinet. The handcart can be pushed in and pulled out with remarkable ease and exhibits excellent interchangeability. The equipment features an aesthetically pleasing appearance, a comprehensive range of configurations, and ensures safe and reliable operation.

Category:

High Voltage Switchgear


Product Overview

  The KYN61-40.5 type armored withdrawable AC metal-clad switchgear is characterized by the use of a fully insulated vacuum circuit breaker of model ZN85-40.5 and a spring-operated mechanism within the cabinet. It can also be equipped with ABB’s VD4-40.5 and HD4-40.5 switchgear units. The switchgear enclosure is assembled from aluminized-zinc coated steel sheets and cold-rolled steel plates with powder-coating, which enhances the precision of the coordination between the handcart and the cabinet. As a result, pushing in and pulling out the handcart is remarkably smooth and effortless, and the handcarts are highly interchangeable. The equipment features an aesthetically pleasing appearance, a comprehensive range of configurations, and ensures safe and reliable operation.

  This product is designed for use in 35kV three-phase AC 50Hz power systems, serving as a device for receiving and distributing electrical energy in substations, power plants, and distribution rooms of industrial and mining enterprises. It features functions such as control, protection, and monitoring.

  This product complies with the following standards: GB3906 “AC Metal-Enclosed Switchgear Rated from 3 to 35 kV,” GB/T 19992 “Common Technical Requirements for High-Voltage Switchgear and Control Equipment,” DL/T404 “Technical Specifications for Ordering AC High-Voltage Switchgear,” and IEC60298 “AC Metal-Enclosed Switchgear and Control Equipment Rated from 1 kV to 52 kV.”

 

Model and Meaning

 

Operating environment conditions

  ◆ Ambient air temperature: -15℃ to +40℃;

  ◆ Altitude: 2000 m and below;

  ◆Humidity conditions: The daily average humidity shall not exceed 95%; the daily average vapor pressure shall not exceed 2.2 kPa; the monthly average humidity shall not exceed 90%; and the monthly average vapor pressure shall not exceed 1.8 kPa.

  ◆ Seismic intensity: Not exceeding 8 degrees;

  ◆ Locations free from obvious contamination such as corrosive or flammable gases. Note: If the operating conditions exceed the above-mentioned normal usage specifications, users may consult with our company.

 

Main Technical Parameters

Technical Parameters of KYN61-40.5 Switchgear
Name Unit Data
Rated voltage KV 40.5
Rated current Main bus rated current A 630, 1250, 1600
Rated current of the circuit breaker to be used A 630, 1250, 1600
Rated insulation level 1 min power frequency withstand voltage, between electrodes, between electrode and ground / between disconnecting elements KV 95/110
Lightning impulse withstand voltage (peak), between electrodes, between poles/inter-pole KV 185/215
Power-frequency withstand voltage of auxiliary circuits and control circuits V/1min 2000
Rated frequency Hertz 50
Rated short-circuit breaking current kA 20, 25, 31.5
Rated short-time withstand current, rated short-circuit duration It's Ka/4S 20, 25, 31.5
Rated peak withstand current kA 50, 63, 80
Rated short-circuit making current kA 50, 63, 80
Rated voltage of the control circuit V DC: 110220, AC: 110220
Protection level Switchgear enclosure   IP4X
Between compartments (when the cabinet door is open)   IP2X

 

Technical Parameters of ZN85-40.5 Circuit Breaker with Spring Operating Mechanism (Integrated)
Name Unit Data
Rated voltage KV 40.5
Rated current A 630, 1250, 1600
Rated insulation level 1 min power-frequency withstand voltage, between electrodes, between electrode and ground/arc-extinguishing gap KV 95/110
Lightning impulse withstand voltage (peak), between electrodes, between poles/break points KV 185/215
Power-frequency withstand voltage of auxiliary circuits and control circuits V/1min 2000
Rated frequency Hertz 50
Rated short-circuit breaking current kA 20, 25, 31.5
Rated short-circuit making current kA 50, 63, 80
Rated peak withstand current kA 50, 63, 80
Rated short-time withstand current, rated short-circuit duration Ka/4S 20, 25, 31.5
Mechanical life Next 10000
Closing time Ms. 50 ~ 100
Trip time Ms. 35 ~ 60
Rated operating sequence   Split - 0.3s - Merge Split - 180s - Merge Split