YBM22-12/0.4 Outdoor Prefabricated Substation


The YBM22 series prefabricated substations integrate high-voltage switchgear, transformers, low-voltage switchgear, and other equipment into a compact, complete distribution unit. They are designed for use in urban high-rise buildings, urban-rural complexes, residential communities, high-tech development zones, small and medium-sized factories, mines, oilfields, and temporary construction sites—serving as devices for receiving and distributing electrical energy within power distribution systems. This product features strong integration, compact size, a streamlined structure, safe and reliable operation, convenient maintenance, and mobility. Compared to conventional civil-engineering substations, a packaged substation of the same capacity typically occupies only 1/10 to 1/5 of the land area required by a conventional substation, significantly reducing design and construction workload as well as capital expenditure. In power distribution systems, these substations can be used in ring network configurations or in dual-power or radial-terminal distribution systems. They represent a new type of complete equipment for both new construction and renovation of substations in urban and rural areas. The YBM22 series prefabricated substations comply with the national standard GB/T17467-1998, "High-Voltage/Low-Voltage Prefabricated Substations."

Category:

Box-Type Substation


Product Overview

  The YBM22 series prefabricated substations integrate high-voltage switchgear, transformers, low-voltage switchgear, and other components into a compact, complete distribution unit. They are designed for use in urban high-rise buildings, urban-rural complexes, residential communities, high-tech development zones, small and medium-sized factories, mines, oilfields, and temporary construction sites, serving as equipment for receiving and distributing electrical energy within power distribution systems. This product features strong integration, compact size, a streamlined structure, safe and reliable operation, convenient maintenance, and mobility. Compared with conventional civil-engineering substations, a packaged substation of the same capacity typically occupies only 1/10 to 1/5 of the land area required by a conventional substation, significantly reducing design and construction workload as well as capital expenditure. In power distribution systems, these substations can be used in ring network configurations or in dual-power or radial-terminal distribution systems. They represent a new type of complete equipment for both new construction and renovation of urban and rural substations. The YBM22 series prefabricated substations comply with the national standard GB/T17467-1998, "High-Voltage/Low-Voltage Prefabricated Substations."

Model and Meaning

 

Operating environment conditions

◆ Air temperature: Upper limit ≤ 40 ℃, lower limit ≥ -10 ℃;

◆ Solar radiation: ≤ 1000 W/m² 2;

◆ Altitude: ≤ 1000 m;

◆ Ice cover: ≤ 20 mm;

◆ Wind speed: ≤ 35 m/s;

◆ Humidity: Daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%, daily average vapor pressure ≤ 2.2 kPa, monthly average vapor pressure ≤ 1.8 kPa;

◆ Earthquake: ≤ Grade 8;

◆ Locations free from fire hazards, explosion risks, severe pollution, chemical corrosion, and intense vibrations.

Note: For special operating conditions, it is recommended to consult with the manufacturer when placing an order.

Main Technical Parameters

Main Technical Parameters
Serial number Name Unit High-voltage electrical equipment Transformer Low-voltage electrical equipment
1 Rated voltage kV 10 10/0.4 0.4
2 Rated current A 630   100 ~ 2500
3 Rated frequency Hertz 50 50 50
4 Rated capacity kilovolt-ampere   100 ~ 1250  
5 Rated thermal stability current kA 20/4S   30/1S
6 Rated dynamic stability current (peak) kA 50   63
7 Rated Closing Short-Circuit Current (Peak) kA 50   15 ~ 30
8 Rated short-circuit breaking current kA 31.5 (fuse)    
9 Rated breaking load current A 630    
10 1-minute power frequency withstand voltage kV 42 breaks between ground and phase, 48 between phases 35/28 (5 min) 20/2.5
11 Lightning impulse withstand voltage kV 75 between ground and phase, 85 between phases 75  
12 Enclosure protection rating   IP23 IP23 IP23
13 Noise level dB   Oil-immersed transformer: 55; Dry-type transformer: 65  
14 Number of circuits one 1 to 6 2 4 ~ 30
15 Maximum reactive power compensation on the low-voltage side Four     300