YBM22-12/0.4 Outdoor Prefabricated Substation
Category:
Box-Type Substation
Tel:
E-mail:
Introduction
Product Overview
The YBM22 series prefabricated substations integrate high-voltage switchgear, transformers, low-voltage switchgear, and other components into a compact, complete distribution unit. They are designed for use in urban high-rise buildings, urban-rural complexes, residential communities, high-tech development zones, small and medium-sized factories, mines, oilfields, and temporary construction sites, serving as equipment for receiving and distributing electrical energy within power distribution systems. This product features strong integration, compact size, a streamlined structure, safe and reliable operation, convenient maintenance, and mobility. Compared with conventional civil-engineering substations, a packaged substation of the same capacity typically occupies only 1/10 to 1/5 of the land area required by a conventional substation, significantly reducing design and construction workload as well as capital expenditure. In power distribution systems, these substations can be used in ring network configurations or in dual-power or radial-terminal distribution systems. They represent a new type of complete equipment for both new construction and renovation of urban and rural substations. The YBM22 series prefabricated substations comply with the national standard GB/T17467-1998, "High-Voltage/Low-Voltage Prefabricated Substations."
Model and Meaning


Operating environment conditions
◆ Air temperature: Upper limit ≤ 40 ℃, lower limit ≥ -10 ℃;
◆ Solar radiation: ≤ 1000 W/m² 2;
◆ Altitude: ≤ 1000 m;
◆ Ice cover: ≤ 20 mm;
◆ Wind speed: ≤ 35 m/s;
◆ Humidity: Daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%, daily average vapor pressure ≤ 2.2 kPa, monthly average vapor pressure ≤ 1.8 kPa;
◆ Earthquake: ≤ Grade 8;
◆ Locations free from fire hazards, explosion risks, severe pollution, chemical corrosion, and intense vibrations.
Note: For special operating conditions, it is recommended to consult with the manufacturer when placing an order.
Main Technical Parameters
| Main Technical Parameters | |||||
| Serial number | Name | Unit | High-voltage electrical equipment | Transformer | Low-voltage electrical equipment |
| 1 | Rated voltage | kV | 10 | 10/0.4 | 0.4 |
| 2 | Rated current | A | 630 | 100 ~ 2500 | |
| 3 | Rated frequency | Hertz | 50 | 50 | 50 |
| 4 | Rated capacity | kilovolt-ampere | 100 ~ 1250 | ||
| 5 | Rated thermal stability current | kA | 20/4S | 30/1S | |
| 6 | Rated dynamic stability current (peak) | kA | 50 | 63 | |
| 7 | Rated Closing Short-Circuit Current (Peak) | kA | 50 | 15 ~ 30 | |
| 8 | Rated short-circuit breaking current | kA | 31.5 (fuse) | ||
| 9 | Rated breaking load current | A | 630 | ||
| 10 | 1-minute power frequency withstand voltage | kV | 42 breaks between ground and phase, 48 between phases | 35/28 (5 min) | 20/2.5 |
| 11 | Lightning impulse withstand voltage | kV | 75 between ground and phase, 85 between phases | 75 | |
| 12 | Enclosure protection rating | IP23 | IP23 | IP23 | |
| 13 | Noise level | dB | Oil-immersed transformer: 55; Dry-type transformer: 65 | ||
| 14 | Number of circuits | one | 1 to 6 | 2 | 4 ~ 30 |
| 15 | Maximum reactive power compensation on the low-voltage side | Four | 300 | ||
Key words:
Box-Type Substation