Photovoltaic combiner box
Category:
PV New Energy Grid Cabinet
Tel:
E-mail:
Introduction
This product is primarily used for collecting power from string inverters in centralized photovoltaic grid-connected power generation systems. It is connected in series between the string-type grid-connected inverter and the grid-metering cabinet. The product features protections such as input surge protection and overcurrent protection for the system. By reducing the need for long-distance transmission of large cable runs, this product helps users lower costs and improve system efficiency. The product has obtained industry-standard certifications including CCC certification, CE certification, and ISO9001 quality management system certification.
Main features
All components are sourced from well-known domestic and international brands, certified by authoritative institutions, and fully qualified. Exposed live parts inside the enclosure are protected by transparent covers made of flame-retardant, antistatic, and high-temperature-resistant materials. Both incoming and outgoing circuit breakers are installed vertically facing forward and laid flat within the enclosure, with wiring connections precisely matched to avoid miswiring. The main busbars are connected using copper bars, whose surfaces have undergone a tinning process that provides corrosion and oxidation resistance. Each phase conductor is marked with colors commonly used in the industry for clear and conspicuous identification. An optional smart monitoring system is available, providing real-time data on system voltage, main busbar current, switch status, and lightning protection status. This product is suitable for various voltage levels in the industry: 380Vac, 480Vac, and 540Vac. It features a rainproof cover design, making it ideal for outdoor installation.
Supports special requirements and custom feature development.
Technical Parameters
| Product Model |
JXF |
|
| Common string inverter power |
5, 10, 15, 20, 25, 30, 40, 50, 60, 80, 100, 110, 125, 175 kW |
|
| Inverter input channels |
Route 1 to Route N (customized on demand) |
|
| Total number of AC output channels |
Route 1 |
|
| Convergence requirements |
Single-phase and three-phase busbar assembly |
|
| System voltage (optional) |
AC: 220V, AC: 380V, AC: 540V, AC: 800V |
|
| Branch circuit switch housing (optional) |
32A, 63A, 80A, 100A, 125A, 160A 200A, 250A, 400A, 630A, 800A |
|
| Switch brand (optional) |
Delixi, Chint, Changshu, Liangxin, ABB, Schneider |
|
| Protection function |
||
| Short-circuit protection |
There is |
|
| Overload protection |
There is |
|
| Lightning protection |
With (nominal current: In: 20 kA, Imax: 40 kA, Up ≤ 4 kV) |
|
| Lightning protection failure protection |
There is |
|
| Environmentally suitable |
||
| Temperature and humidity |
Operating temperature: -25 to +60℃ Storage temperature: -40 to +70℃ Humidity: 0-90% with no condensation or frost Areas free of corrosive gases (please specify if any exist) |
|
| Product Model |
JXF |
|
| Use altitude |
≤2000M |
|
| Safety regulations |
||
| Copper Busbar Selection |
Copper busbar (tin-plated industrial) |
|
| Security protection |
PVC protective board |
|
| Electrical clearance |
≥14mm |
|
| Creepage distance |
≥25mm |
|
| Insulation resistance |
>20 MΩ |
|
| Insulation voltage |
AC 3000V, 1 MIN |
|
| Regular parameters |
||
| Box material |
Stainless steel, cold-rolled sheet with plastic coating, stainless steel with plastic coating |
|
| Protection level |
Outdoor IP65 |
|
| Box type |
Single-door distribution box |
|
| Installation method |
Wall-mounted / Floor-standing (customizable) |
|
| Box dimensions (length × width × height) |
Customized on demand |
|
Wiring Diagram and Layout Diagram of the DC Combiner Box